Permit Information
Permit NumberELE17-00099
StatusFinaled
Name TWIN CITIES ELECTRIC
Site Address 1425 N CLOVERDALE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: INSTALL WIRING FOR STORAGE FACILITY
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/19/20176/20/20176/20/2017APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...

corrections made...ok to final
Final6/7/20176/8/20176/8/2017PFAIL
DetailsTom Saunders
please inspect after 9;30 am Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON

1) available fault current labelling on service
2) outside panels need labelled completely...
front and back panels
3) outlet below outside panel shows hot neutral reverse
4) service shall have a intersystem bond bar
5) access to roof units needed to verify labelling, disconnects, breaker size, service outlet, etc.
contractor will provide a sturdy ladder or sometime of means for access to roof
Final5/26/20175/30/20175/30/2017ANR
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...

will recall in when ready
Final4/28/20175/1/20175/1/2017ACANC
DetailsTom Saunders
inspection is for fist storage unit building behind the office Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...

this permit is only associated with office building...contractor has been notified that he must pull a seperate electrical permit for each building and have it associated to each seperate building permit
Electrical Rough-In2/20/20172/21/20172/21/2017APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...

ok to cover....office space...back storage units connected to this building will still need rough in inspection
Electrical Rough-In1/18/20171/19/20171/19/2017APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON....

discussed with contractor reason for no inspections on underground piping and grounding for srevice...contractor sent 7 pictures...pictures include picture of pipes depth, tape measure verifying, size/type of pipes, length of ground wire and its connections to rebar, pictures can be verified of location with surrounding sceneries, gave warning for all future inspections
Permanent Service1/19/20171/19/20171/19/2017APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON....

p/s u/g n ok