Permit Information
Permit NumberELE17-00129
StatusFinaled
Name APEX ELECTRIC INC
Site Address 1911 S ABBS ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: wire mother in law house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/21/20173/21/20173/21/2017PPASS
DetailsEric Story
Reinspect Phone #: ###-#### Inspection requested via web by Greg Idsinga
Corrections fixed final ok
Final3/20/20173/20/20173/20/2017PFAIL
DetailsEric Story
House in back of main home. Phone #: ###-#### Inspection requested via web by Greg Idsinga
210.8 Receptalces located within 6' of a sink shall have GFCI protection
110.25 lockout needed fro water heater or disc
344.30 RMC shall have support within 3' of panel
110.30 fix both w/p's
Permanent Service2/1/20172/1/20172/1/2017APASS
DetailsEric Story
corrections Phone #: ###-#### Inspection requested via web by Greg Idsinga
p/s o/h n ok
Rough-In Permanent Service1/20/20171/20/20171/20/2017PCANC
DetailsEric Story
Mother in law quarters in the back Phone #: ###-#### Inspection requested via web by Greg Idsinga
Just rough-in at this time
Electrical Rough-In1/20/20171/20/20171/20/2017PPASS
DetailsEric Story
Mother in law quarters in the back Phone #: ###-#### Inspection requested via web by Greg Idsinga
Mother in law quarters ok cover
Permanent Service1/20/20171/20/20171/20/2017PFAIL
DetailsEric Story
Mother in law quarters in the back Phone #: ###-#### Inspection requested via web by Greg Idsinga
408.36(d) Back fed devices shall be fastened in place(screw missing in main)
230.24 Shall maintain 18' from service drip loop to roof line