Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberELE17-00156
StatusFinaled
Name PRIMARY ELECTRIC
Site Address 7199 W FAIRVIEW AVE
Project Name 
Customer Number9903
ePlanReviewNo
Description
Addition: Provide a 277/480V 200 amp 3 phase service
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/22/20172/23/20172/23/2017APASS
DetailsTom Saunders
Todd Sellman is contact at ###-####. If he cannot be reached, call Mike Rossknecht at ###-#### Phone #: ###-#### Inspection requested via web by Todd Sellman...

clearances obtained...no corrections needed...ok to final
Rough-In Permanent Service1/24/20171/24/20171/24/2017PNR
DetailsTom Saunders
Contact on site is Mike. This is just for the outside portion including the underground. Phone #: ###-#### Inspection requested via web by Todd Sellman...

disconnect mounted ok...no transformer set yet
Electrical Rough-In1/24/20171/24/20171/24/2017PPASS
DetailsTom Saunders
Mike Phone #: ###-####....

ok to cover pipes to transformer
Conference1/23/20171/23/20171/23/2017PDONE
DetailsRock A. Hudson
Please contact Todd Sellman to meet onsite for conference. ###-####. Phone #: ###-#### Inspection requested via web by Todd Sellman
Contactor to add new 480 volt service to building. CT meter at outdoor transformer. Main disconnecting means outside on south side. Once on inside plans are to install a gutter to tap off and refeed existing disconnects.
Issues
BCC 4-05-32- Code violations not to be retained.
110.26(A)- Minimum work space shall be provided for all disconnecting means. 36" deep and 30" wide.
110.26(B)- Work space shall be clear of foriegn equipment, compressor encroaches on space.
404.8(A)- Max height of disconnecting means shall not exceed 6'7".