Final | 8/15/2017 | 8/15/2017 | 8/15/2017 | P | PASS |
James Ady
|
|
|
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
Rough-In Permanent Service | 6/9/2017 | 6/9/2017 | 6/9/2017 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn p/s u/g n ok. All corrections made.
|
Rough-In Permanent Service | 6/8/2017 | 6/9/2017 | 6/9/2017 | A | FAIL |
Rock A. Hudson
|
|
|
ready now. thanks Phone #: ###-#### Inspection requested via web by Bob Glenn 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. Nail plated needed. Pantry notched stud, Master bed upper plate between windows, spare bed inside closet. 422.11- Furnace branch circuit shall be 20 amp as per manufacturers instructions.
|