Final | 8/16/2017 | 8/17/2017 | 8/17/2017 | A | PASS |
James Ady
|
|
|
garage code 0524 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
Electrical Rough-In | 5/17/2017 | 5/18/2017 | 5/18/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover
|
Permanent Service | 5/18/2017 | 5/18/2017 | 5/18/2017 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn p/s u/g n ok
|
Rough-In Permanent Service | 5/16/2017 | 5/17/2017 | 5/17/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.52(I)- Entry way or foyer over 60 sq. ft. shall have a receptacle outlet installed on walls 3' wide or more. 240.24- Operating handle of a over current device shall not be higher than 6'7". 250.134- Metal box in net panel shall be connected to equipment grounding conductor. 300.4- NM coble shall be protected from physical damage where run thru bored hole that does not maintain 1 1/4" from framing surface. 10-3 below panel to left outer wall.
|