Permit Information
Permit NumberELE17-01861
StatusFinaled
Name PERRINE ELECTRIC
Site Address 2737 S BARNSIDE WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: New home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/10/201710/11/201710/11/2017APASS
DetailsJames Ady
Code 2010 Phone #: ###-#### Inspection requested via web by danny perrine Corrections made final ok
Final10/5/201710/5/201710/5/2017PFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by danny perrine 210.52 A 2. Wall more than 2ft shall have recep. (Behind master bed door) Hood not installed. Exposed romex hanging in opening.
Electrical Rough-In6/27/20176/28/20176/28/2017PCANC
DetailsJames Ady
Soffit cans only Phone #: ###-#### Inspection requested via web by danny perrine Called in wrong permit
Rough-In Permanent Service6/20/20176/21/20176/21/2017APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by danny perrine Corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service6/19/20176/20/20176/20/2017AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by danny perrine
210.52- Up loft receptacles more than 12' apart. Shelving being installed on these walls.
314.17(C)- NM cable sheath shall enter box minimum of 1/4". Smoke by stair.
334.30- MN cable shall be secured with in 12" of a box or stub. Pool wire, AC wire, WP of garage, entry recept., sunroom under window.
422.12- Furnace max amperage 14.8 amp x 125%= 18.5, 20 amp circuit required.
300.4- Nail plates needed where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface.
James said OK to foam seal.