Permit Information
Permit NumberELE17-02025
StatusFinaled
Name GLENN ELECTRIC
Site Address 5757 E HOOTOWL DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: ROUGH AND PERM. SERVICE
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/18/201710/19/201710/19/2017APASS
DetailsRock A. Hudson
code 4224 any ? call bill ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
Final10/12/201710/13/201710/13/2017AFAIL
DetailsRock A. Hudson
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn 404.9, 406.6- All switch and receptacle outlet covers shall be installed. Several removed.
Rough-In Permanent Service7/5/20177/5/20177/5/2017PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Bob Glenn Corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service7/4/20177/5/20177/5/2017AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Bob Glenn
110.3- Fireplace igniter wire shall be secured as to not be in contact with fireplace shell as per manufacurers instructions.
210.52- Tech room receptacle outlet shall be added to serve wall space with in 6' of left side of door.
210.52- Up family room shall have receptacle outlets added to serve wall space created by rail.
800.24- Communication wires shal be installed in a manner so they are not subject to physical damage. Upstairs hanging below ceiling.