Permit Information
Permit NumberELE17-02042
StatusFinaled
Name POWERBOUND ELECTRIC INC
Site Address 1157 E RUBICON DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/5/201710/5/201710/5/2017PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by steve cooper corrections made final ok
Final10/3/201710/4/201710/4/2017AFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by steve cooper GFCI test on floor heat T stat not functioning. 210.11 C2 and C3. Laundry room 20 Branch circuit shall have no other outlets, Bathroom 20 branch circuit shall have no other outlets.
Rough-In Permanent Service7/20/20177/21/20177/21/2017APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by steve cooper
Rough in ok cover p/s u/g n ok
Electrical Rough-In7/19/20177/20/20177/20/2017AFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by steve cooper 110.14B Splices shall be made by identified devices. Smoke detector grounds. 300.4A1 Bored holes less than 1 1/4in need nail plates. ( Up bed wall next to laundry) 300.4 D Cables shall be supported 1 1/4in away from face of stud. Laundry counter recep, Up bath 2 gang.