Permit Information
Permit NumberELE17-02381
StatusFinaled
Name KAMM SCOTT
Site Address 7089 N DUNCAN LN
Project Name 
Customer Number 
ePlanReviewNo
Description
re-locating existing outlets as part of interior remodel, new exhaust fans in bathrooms
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/2/201912/2/201912/2/2019PPASS
DetailsMark Moncarr
Scott Phone #: ###-#### Ok final. Items addressed were corrected.
Final11/7/201911/8/201911/8/2019ANR
DetailsMark Moncarr
Scott Phone #: ###-#### 1 recept entry not working. GFI in bed for 2 recpets within 6' of sink. Strap needed for AC, filler piece needed for siding where outside recept is located.
ELE-Aging Inspection10/8/201910/8/201910/9/2019 DONE
DetailsMark Moncarr
Please schedule a final inspection.
ELE-Request for Extension4/9/20197/19/20197/19/2019APASS
DetailsDaryl DeGrange
This request for extension counts as two Requests, ok until 7/19/2019 A required inspection will need to be requested & passed in order to update the permit 180 days; Phone #: ###-#### job still under construction, Extension request ok
ELE-Aging Inspection7/9/20197/9/20197/9/2019 DONE
DetailsMark Moncarr
Please call with progress on job or schedule a final inspection.
Electrical Rough-In9/12/20179/13/20179/13/2017APASS
DetailsMark Moncarr
Scott Phone #: ###-#### p/s o/h rec ok
Electrical Rough-In8/31/20179/1/20179/1/2017APASS
DetailsMark Moncarr
Scott Phone #: ###-#### Ok cover
Conference7/24/20177/25/20177/25/2017ADONE
DetailsRock A. Hudson
Please call ahead for access - Scott Phone #: ###-####
Discussed all codes covering residential wiring. Service change required due to unfused conductors entering structure. Discussed mast, disconnect, grounding electrode system, plumbing and ground rod. Panel location is partially covered by water heater, new location required, mey use as junction point. Talked receptacle spacing for habitable rooms and kitchen counter top areas and bathroom dedicated 20 amp and location. All junction points shall be accessible, saw old and new splices. Discussed tamper resistant type and weather resistant type receptacles. GFCI protection for all bath, outdoor, kitchen counter top receptacles, AFCI protection for new wiring in bedrooms, only new in master bed planned. Scope of work to include new master bed and bath, kitchen area, laundry area and service.
Informed homeowners are required to do work with help from immediate family only.