Permit Information
Permit NumberELE17-02434
StatusExpired
Name AHERN DENNIS
Site Address 4507 W FREEMONT ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Alteration or Repair: Replace 100 amp service with updated 200 amp service.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection10/9/201910/9/201910/11/2019 FAIL
DetailsRock A. Hudson
No response from previous attemps.
Doc expired
DOC - Permit Expired10/11/201910/11/201910/11/2019PPASS
DetailsRock A. Hudson
Doc expire OK
ELE-Aging Inspection7/9/20197/9/20197/17/2019 FAIL
DetailsRock A. Hudson
Called owner, no answer, left message about open permit on property and asked to request a final inspection or call to inform of progress of job.
Electrical Rough-In12/5/201712/5/201712/5/2017PPASS
DetailsRock A. Hudson
I should be ready after 12:00 to have you reinspect. If you give me call I''ll make sure I''m there. Thanks for working with me on this! Phone #: ###-#### Inspection requested via web by Dennis Ahern p/s o/h rec ok
Rough-In Permanent Service12/4/201712/5/201712/5/2017AFAIL
DetailsRock A. Hudson
I''m replacing my panel today and would like an inspection late in the day to make sure I get it all in. Please call ahead to confirm I am ready for inspection. Thanks! 208 841 7286. Phone #: ###-#### Conference noted on ELE17-02435. 200.6- Grounded conductors larger than #6 shall be identified with white markings at terminations points.
250.24- Grounding electrode system shall be connected to grounded conductor a main disconnecting means.
250.52- Ground rod gronding electrode system shall be supplemented by additional rod or metal piping system.
250.66- If metal underground water pipe present a minimum of #4 copper grounding electrode conductor shall connect with in 5' of entrance to crawl space.
358.30, 42- Emt Connectors shall be tight and shall be secured with in 3' of top and bottom.
Rough-In Permanent Service12/4/201712/4/201712/4/2017PNR
DetailsRock A. Hudson
I''m replacing my panel today and would like an inspection late in the day to make sure I get it all in. Please call ahead to confirm I am ready for inspection. Thanks! 208 841 7286. Phone #: ###-#### Inspection requested via web by Dennis Ahern
Called contact to check on progress and was asked to reschedule for next day in AM due to not being ready.