Permit NumberELE17-02575
StatusFinaled
Name HOOD ELECTRIC
Site Address 8820 W FIRCREST DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Install 60 amp sub panel in new shop. Intalll receptacles, switches and lighting per building permit plans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/11/20179/12/20179/12/2017APASS
DetailsRock A. Hudson
Call half hour before I can meet you there. Thanks Phone #: ###-#### Inspection requested via web by mark hood
Final ok
Final9/11/20179/11/20179/11/2017PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by mark hood
210.8- All devices providing GFCI protection shall be located in a readily accessible location.
300.15- A box shall be installed at all splice points. Flood light located on house garage soffit hanging on wires without a box at time of inspection.
BCC 4-05-32- Code violations not to be retained.
406.9(B)(1)- All 15 and 20 amp 120 volt receptacle outlets located in a wet location shall be (WR) weather resistant type.
Electrical Rough-In8/23/20178/23/20178/23/2017PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by mark hood....

rough ok to cover