Permit Information
Permit NumberELE17-02733
StatusFinaled
Name GOLDEN ELECTRIC
Site Address 1309 N 5TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Rewire residence; new sub panel and new exterior panel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/31/20182/1/20181/31/2018APASS
DetailsMark Moncarr
###-#### John. Ok final. Corrections made. Looked at on 1/31/18. Recept in bath off kitchen was protected by a GFI in the mech. room. Contractor installed GFI in bath and blanked recept in mech. room.
Final1/31/20181/31/20181/31/2018PCANC
DetailsMark Moncarr
John is on site and has corrections made Phone #: ###-#### Inspection requested via web by John Harvey Re-scheduled for 2/1/18
Final1/29/20181/29/20181/29/2018PFAIL
DetailsMark Moncarr
Call john if any problems.

Key is hanging in the front left corner of the porch Phone #: ###-#### Inspection requested via web by John Harvey
1. Recept on corner of living/dining wall has open neutral.
2. Mstr bed not ARC fault protected.
3. GFI for bath off kitchen is located in basement mech room. Dedicated bath circuit cannot leave bath unless feeding another outlet in another bath.
4. Lockouts needed for appliances. Hood/DW/oven/micro.
Rough-In Permanent Service12/19/201712/20/201712/20/2017APASS
DetailsMark Moncarr
Conduit has been installed. Call john if any issues. Will be there by 9am Phone #: ###-#### Inspection requested via web by John Harvey p/s o/h n ok. Correction made. Conduit installed from meter main to basement panel.
Rough-In Permanent Service12/18/201712/19/201712/19/2017AFAIL
DetailsMark Moncarr
Call john if any problems Phone #: ###-#### Inspection requested via web by John Harvey 2" conduit is not a full run to panel in basement. THHN is laying on floor of crawl space. Either continue conduit completely to basement panel, or pull SER to feed panel.
Electrical Rough-In8/23/20178/23/20178/23/2017APASS
DetailsMark Moncarr
Call john if any issues Phone #: ###-#### Inspection requested via web by John Harvey Ok cover. Corrections made.
Electrical Rough-In8/21/20178/22/20178/22/2017AFAIL
DetailsRock A. Hudson
Call John if any issues. Thanks. Phone #: ###-#### Inspection requested via web by John Harvey
210.52(A)- Dn bed all walls 24" or wider shall have a receptacle outlet installed.
300.4- Where NM cable is run thru bored or notched holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates.
334.30- NM cable shall be supported at intervals not to exceed 4 1/2' and be secured with in 12" of a box. Back can and kitchen boxes.