Permit Information
Permit NumberELE17-03398
StatusFinaled
Name 45TH PARALLEL ELECTRIC LLC
Site Address 5143 W CAMAS ST
Project Name 
Customer Number33033
ePlanReviewNo
Description
Alteration or Repair: electrical courtesy inspection
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/12/20181/12/20181/12/2018PPASS
DetailsEric Story
Unit 5144 Phone #: ###-#### Inspection requested via web by David Nelson
Correction fixed final ok
Final1/12/20181/12/20181/12/2018AFAIL
DetailsEric Story
406 Receptacle replacement with open ground shall be GFCI protected and identified as open ground and Ground fault protected. Rest of unit check out fine
Conference10/9/201710/10/201710/10/2017ADONE
DetailsRock A. Hudson
Would like to meet inspector on site, please call with ETA ###-####.
Thank you. Phone #: ###-#### Inspection requested via web by David Nelson
Discussed required wiring of fire damaged appartments. All wiring damaged by heat or water shall be replaced as needed. Where units have totally opened up walls and ceilings, wiring shall be replaced to all new codes. Areas with only smoke damage not required to be brought up to code due to wiring not being replaced.
BCC 4-05-32 Code violations not to be retained. City ordinance requires code violations to be repaired even if damage is not present. Found paddle fans installed on boxes not rated for fans and microwaves installed on general lighting circuits with splice buried in walls. If fans to remain listed boxes shall be installed. Circuits shall be added for microwaves or hoods shall be istalled to eliminate overloads. If additional life safety code violations are found during rebuild they shall be repaired.