Permit Information
Permit NumberELE17-03984
StatusFinaled
Name SPENCER ELECTRIC
Site Address 1075 E PARK BLVD
Project NameSt Lukes CMHC - Int Remodel
Customer Number 
ePlanReviewNo
Description
tenant remodel - complete
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/18/20183/19/20183/19/2018APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by ron spen cer corrections made final ok
Final3/13/20183/14/20183/14/2018PFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by ron spen cer 406.12 Offices and corridors in patient care facilities shall be tamper resistant,(areas marked on print.) 210.8 Receps within 6ft of a sink shall be gfci protected. 210.8 GFCI shall be readily accessable( Drinking fountain) Floor recep in back conference room showing open ground
Final3/7/20183/8/20183/8/2018ANR
DetailsJames Ady
partial final--above grid inspection Phone #: ###-#### Inspection requested via web by ron spen cer
Electrical Rough-In3/8/20183/8/20183/8/2018PPASS
DetailsJames Ady
partial final--above grid inspection Phone #: ###-#### Inspection requested via web by ron spen cer Ceiling only ok to cover
Electrical Rough-In12/27/201712/28/201712/28/2017APASS
DetailsMark Moncarr
floor boxes--3 conference rooms Phone #: ###-#### Inspection requested via web by ron spen cer Ok cover floor boxes. 2 NW corner, and 1 SE corner.
Electrical Rough-In12/20/201712/21/201712/21/2017PPART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by ron spen cer
3 walls marked on contractor print will be left open due to meeting rooms will require floor receptacles as per NEC 210.71. 2 meeting rooms large enough needed 2 floor receptacles. Will call for inspection for these 3 walls when ready. Rest of walls and hard lids rough in ok cover.