Permit Information
Permit NumberELE17-04057
StatusFinaled
Name TREASURE VALLEY ELECTRIC INC
Site Address 10539 W OVERLAND RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Tenant improvement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/28/20181/29/20181/29/2018APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Steve Craig...corrections made...ok to final
Final1/24/20181/25/20181/25/2018PFAIL
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Steve Craig....1)
all outlets need completed with power-outlets below counter have no power, unable to verify GFI protection
2) OCPD on hot wells are too large-15A max on nameplate
3) roof top units need labelled
4) cooler cases need finished, outlets need mounted to proper cover plates-2 of them
Final1/23/20181/24/20181/24/2018AFAIL
DetailsTom Saunders
Final inspection for kitchen addition in existing building Inspection requested via web by Steve Craig...miscellaneous equipment not hooked up need finished, outlets no power, outlet needs moved...cannot modify plate, breakers not on in panel...reason?, breaker lockouts need installed on ocpd of hard wired appliances
Electrical Rough-In1/19/20181/19/20181/19/2018PPASS
DetailsMark Moncarr
Ceiling cover inspection in kitchen and prep room Phone #: ###-#### Inspection requested via web by Steve Craig Ok cover kitch and prep area ceilings.
Electrical Rough-In12/17/201712/18/201712/18/2017APASS
DetailsRock A. Hudson
call one half hour before inspection to ensure building is unlocked Phone #: ###-#### Inspection requested via web by Steve Craig
Wall rough in ok cover
Electrical Rough-In12/14/201712/15/201712/15/2017AFAIL
DetailsDaryl DeGrange
Call 30 minutes prior to inspection so I can make sure the door is unlocked inspect new steel stud walls for cover Phone #: ###-#### Inspection requested via web by Steve Craig NEC 330.12 (1) MC cable shall not be installed where subject to physical damage. Along inside 2x4 steel stud door frame. 300.5 shall not install MC cable within 1 1/4 of edge of framing member
Electrical Rough-In12/4/201712/4/201712/4/2017PPASS
DetailsTom Saunders
Rough in of 5 floor boxes before concrete por Phone #: ###-#### Inspection requested via web by Steve Craig...ok to cover