Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE17-04207
StatusFinaled
Name J&C ELECTRICAL SOLUTIONS LLC
Site Address 875 E IRONSIDE DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Rewire 2 rooms wire dryer and washer
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/1/20183/2/20183/2/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by cris flores
Final ok
Final2/9/20182/9/20182/9/2018PCANC
DetailsJames Ady
Phone #: ###-#### >> Inspection requested via web by cris flores Inspection cancelled from web by: cris flores
Electrical Rough-In12/14/201712/15/201712/15/2017APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by cris flores corrections made rough in ok
Electrical Rough-In12/14/201712/14/201712/14/2017PFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by cris flores 314.27. Boxes at ceiling paddle fan locations shall be listed for paddle fan support. 210.52. A 2. Wall space. Receps shall not be more than 12ft apart.