Final | 7/2/2018 | 7/2/2018 | 7/2/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Final ok
|
Final | 6/28/2018 | 6/29/2018 | 6/29/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Units locked, up entrance wet tile no access, garages locked. Recall when ready
|
Final | 6/20/2018 | 6/22/2018 | 6/22/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Label main disconnect for west meter pack, secure house panel cover with all screws, All garages no access to receptacles, AFCI will not hold in 102 bed, all front outdoor receptacles shall have GFCI protection, 101 locked no access, 205 shall have a receptacle adjacent to 2nd basin in main bathroom, 205 no access to 1 bed due to door stacked blocking opening, 203 bed receptacle blocked by barn door, 202 barn door not in to check access to receptacles, 201 is staged blocking access to misc receptacles, 201 has art work over panel, no access to roof to check RTUs.
|
Permanent Service | 3/16/2018 | 3/16/2018 | 3/16/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Right side service p/s u/g n ok
|
Permanent Service | 3/15/2018 | 3/15/2018 | 3/15/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Please inspect the new 400amp disconnect and meter base for permanent service. Thank you Phone #: ###-#### Inspection requested via web by Ryan Wilson 250.24(A)(4)- The grounding electrode system shall be connected where the grounded service conductor terminates in the service disconnecting means. 250.24(A)(5)- The grounded conductor shall not be connected to non-current carrying metal parts on the load side of service disconnect. 250.110- Equipment fasted in place. Non-current carrying metal parts shall be connected to an equipment grounding conductor. In meter pack sub gear
|
Permanent Service | 3/7/2018 | 3/8/2018 | 3/8/2018 | P | PASS |
Rock A. Hudson
|
|
|
Please inspect the meter pack on the left. Thanks Phone #: ###-#### Inspection requested via web by Ryan Wilson Available fault current posted 9,987 amp on 10K reated mains. Left service only p/s u/g n ok
|
Permanent Service | 3/5/2018 | 3/6/2018 | 3/5/2018 | P | CANC |
Rock A. Hudson
|
|
|
Left 6 pack only please Phone #: ###-#### >> Inspection requested via web by Ryan Wilson Inspection cancelled from web by: Ryan Wilson
|
Permanent Service | 2/27/2018 | 2/28/2018 | 2/28/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Please inspect the meter base on the left. Phone #: ###-#### Inspection requested via web by Ryan Wilson 110.9- Equipment intended to interupt current at fault levels shall have an interupting rating at least equal to the current that is available at the line terminals of the equipment. 12,081 available and 10k rated main breakers.
|
Electrical Rough-In | 2/5/2018 | 2/6/2018 | 2/6/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Service wall incomplete. All units rough in ok cover
|
Permanent Service | 1/26/2018 | 1/29/2018 | 1/29/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson 110.24- Available fault current shall be posted on all services prior to inspection. 230.71- Shall not exceed 6 means of disconnecting service. Must check for firewall seperating building into 2 seperate 4 unit structures. 250.24- Service shall be connected to a grounding electrode system.
|