Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE18-00491
StatusFinaled
Name R M E INC
Site Address 720 E PARK BLVD Unit: 200
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install Lighting, power , and HVAC connections per plans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/30/20187/31/20187/31/2018APASS
DetailsJames Ady
Danny. Phone #: ###-#### Inspection requested via web by Sean DeLacy final ok
Electrical Rough-In5/15/20185/15/20185/15/2018PPASS
DetailsJames Ady
Ceiling Cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Remaining ceiling in TI ok to cover
Electrical Rough-In5/14/20185/14/20185/14/2018PPASS
DetailsJames Ady
Ceiling Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen remaining offices, ceiling only ok to cover
Electrical Rough-In5/7/20185/7/20185/7/2018PPASS
DetailsRock A. Hudson
Ceiling cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Grid as noted on contractor print rough in ok cover
Electrical Rough-In3/27/20183/28/20183/28/2018PPASS
DetailsRock A. Hudson
Ceiling Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
IT room hardlid only rough in ok cover
Electrical Rough-In3/27/20183/27/20183/27/2018PFAIL
DetailsRock A. Hudson
Ceiling Cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
300.11- Luminaires shall be supported independant of ceiling support system unless manufacturers instructions state ceilling system can handle additional weight.
300.15- All wiring shall terminate in a box and shall be accessible. Conduit with wiring in it, Old disconnect and buried box on perimeter wall.
Electrical Rough-In2/22/20182/23/20182/23/2018PPASS
DetailsEric Story
Wall Cover. Danny is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Walls in Conference rooms ok to cover
Electrical Rough-In2/9/20182/9/20182/9/2018APASS
DetailsRock A. Hudson
Wall cover. Danny is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen
BLD17-03978 history shows plan review received prints 11-1-17, new code adopted 7-1-17 with 60 day grace period. All jobs with plan review complete after 9-1-17 shall comply with 2017 NEC.
210.71- Called contact Dan and left message to inform required floor receptacles and total room receptacle counts are required for this job. Wall rough in ok cover
Electrical Rough-In2/7/20182/7/20182/7/2018AFAIL
DetailsJames Ady
Wall Cover. Danny is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 300.4 F Cable ron within 1 1/4in from face of framing member shall be protected. ( All 2in studs with MC cable ran horizontle shall be nail plated