Final | 3/30/2018 | 3/30/2018 | 3/30/2018 | P | PASS |
Eric Story
|
|
|
We Are Ready For Final, The Owners Are Trying To Get This Done So They Can Start Training And Opening. Its All Ready For Ya Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett Card signed for perm occ, Final ok
|
Conference | 3/30/2018 | 3/30/2018 | 3/30/2018 | A | DONE |
Eric Story
|
|
|
I Am Am Ready To Final Out This Job But, I Want To Give You Some Time To Look At Everything And Make Sure No Surprise Thanks So Much Dave Phone #: ###-#### Inspection requested via web by jason shifflett Discussed requirements at whats needed for final and all checked out just fine.
|
Electrical Rough-In | 3/20/2018 | 3/20/2018 | 3/20/2018 | P | PASS |
Eric Story
|
|
|
We Would Like To Get A Cover Inspection On The Drop Ceilings So They Can Cover Them Up And We Can Button Up Everthing For A Final Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett Suspended ceilings only ok to cover
|
Permanent Service | 2/28/2018 | 2/28/2018 | 2/28/2018 | P | PASS |
Eric Story
|
|
|
I Have The fault Current For The Service From Idaho Power The Highest Values Are As Follows Line To Line Is 7,735 Amps Line To Neutral Is 5.634 Amps Which Keeps Us Well Below The 20 K AIC rating Of The breakers. Ill Make Temp Labels This Morning And Order Permanents For Final Thanks dave Phone #: ###-#### Inspection requested via web by jason shifflett p/s o/h n ok
|
Rough-In Permanent Service | 2/26/2018 | 2/27/2018 | 2/27/2018 | P | CANC |
Eric Story
|
|
|
We Are Ready For Servuce And Cover On The Panel Walls Thanks Phone #: ###-#### Inspection requested via web by jason shifflett
|
Electrical Rough-In | 2/27/2018 | 2/27/2018 | 2/27/2018 | P | PASS |
Eric Story
|
|
|
We Are Ready For Servuce And Cover On The Panel Walls Thanks Phone #: ###-#### Inspection requested via web by jason shifflett Panel wall and adjacent wall only ok to cover
|
Permanent Service | 2/27/2018 | 2/27/2018 | 2/27/2018 | P | FAIL |
Eric Story
|
|
|
We Are Ready For Servuce And Cover On The Panel Walls Thanks Phone #: ###-#### Inspection requested via web by jason shifflett 110.24 Available fault current calc required prior to being energized
|
Permanent Service | 2/26/2018 | 2/27/2018 | 2/26/2018 | A | CANC |
Eric Story
|
|
|
We Need Permanent Service And The Grounding Looked At So Concrete Driveway Can Pour Thanks Dave Phone #: ###-#### >> Inspection requested via web by jason shifflett Inspection cancelled from web by: jason shifflett Inspection cancelled from web by: jason shifflett
|
Electrical Rough-In | 2/13/2018 | 2/14/2018 | 2/14/2018 | P | PASS |
Eric Story
|
|
|
I Need A partial wall Inspection Its Ready Thanks Inspection requested via web by jason shifflett Walls only ok to cover
|