Permit Information
Permit NumberELE18-00569
StatusFinaled
Name L & K ELECTRIC
Site Address 9030 W FRANKLIN RD
Project Name 
Customer NumberBig Smoke
ePlanReviewNo
Description
Alteration: Added outlets under counter.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In4/2/20184/3/20184/3/2018PPASS
DetailsRock A. Hudson
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
Corrections complete Thank you.
Final4/3/20184/3/20184/3/2018PPASS
DetailsRock A. Hudson
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
Electrical Rough-In4/2/20184/4/20184/2/2018ACANC
DetailsTom Saunders
Justin ###-#### Phone #: ###-#### >> Inspection requested via web by Samatha Solberg Inspection cancelled from web by: Samatha Solberg
Final4/2/20184/2/20184/2/2018PFAIL
DetailsRock A. Hudson
2nd notice- Corrections from 2-13-18.
300.15- All wiring shall terminate in a box. Front sign wiring on roof.
330.30(B)- MC shall be secured with in 12" of a box. Under cabinet receptacles.
356.30- Non-metallic seal tight on east condensing unit shall be secured with in 12" of terminations.
404.8- Circuit directories shall be updated. Ensure all wiring not being used disconnected.
314.17(A)- All unused openings shall be closed by approved means. West condencing units removed. Open KOs.
406.6- Receptacles shall have proper covers installed. Back room receptacle recessed in wall with caulking as cover.
7 Working days to complete, will revisit
4-12-18. If not action has been taken a activity hold will be accessed to parcel and no work or inspections will be allowed once accessed.
Manager scanned and forwarded to supervisor while 2nd correction delivered.
Final2/13/20182/13/20182/13/2018PFAIL
DetailsRock A. Hudson
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
300.15- All wiring shall terminate in a box. Roof old sign removed. Open wiring.
330.30(B)- MC shall be secured with in 12" of a box. UC receptacles.
356.30- Non-metallic seal tight on east condensing unit new, shall be secured with in 12" of terminations.
404.8- Circuit directories shall be updated. Ensure all unused circuits have been disconnected.
314.17(A)- All unused openings shall be closed. West condensing units removed.
* Note from Fire Marshal on site states furnace shall be relocated with clearences as per manufacturers spec.
BCC 4-05-32 Code violations not to be retained. As leaving noticed receptacle recessed in wall with out proper cover. Caulking around perimeter of receptacle.