Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE18-00776
StatusFinaled
Name UNITED ELECTRIC CONTRACTING
Site Address 251 E FRONT ST Unit: 100
Project Name 
Customer NumberHAPPY FAM
ePlanReviewNo
Description
Alteration: 200A Sub-Panel; 100A Sub-Panel (Kitchen); New Light Fixtures (Exit & EM Lighting, Pendants, Cans, 2x4, Hi-Bay; Lighting Control, Power, Receps, Switches, Tele/Data Stubbed to Ceiling; USB Outlets; A/V Conduit Chase
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/22/20186/25/20186/25/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by JENNY EMEL
All receptacles in break area are GFCI protected, 4- 2 pole receptacles in lab not required to be GFCI protected due to not being used as a kitchen and not located with in 6' of a sink. Final ok
Electrical Rough-In5/23/20185/24/20185/24/2018APASS
DetailsRock A. Hudson
Rough in panel.

Contact Steve Nuxoll with questions

Thank you and have a nice day!! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Panel board rough in ok cover
Electrical Rough-In5/16/20185/17/20185/17/2018APASS
DetailsRock A. Hudson
Request is for ceiling inspection

Please contact Steve Nuxoll with any questions.

Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Entry and office grid, reception millwork Rough in ok cover. Discussed required clearances for transformer to wall, determined by manufacturers instructions if under 112KVA under 1000 volts. And system bonding jumper location for metallic raceway to be in transformer if equipment ground and system bonding present as per 450.10.
Electrical Rough-In3/5/20183/5/20183/5/2018PPASS
DetailsEric Story
Please contact Steve Nuxoll with any questions.

Have a lovely afternoon! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Shower walls and ceilings only ok to cover
Electrical Rough-In2/28/20183/1/20183/1/2018APASS
DetailsRock A. Hudson
Contact Steve Nuxoll with any questions

Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
5 receptacles in each conference room minimum.
Baths and shower rooms not ready, Rest of walls rough in ok cover.