Final | 6/1/2018 | 6/4/2018 | 6/4/2018 | A | PASS |
James Ady
|
|
|
garage code 4124 Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made final ok
|
Final | 5/30/2018 | 5/31/2018 | 5/31/2018 | A | FAIL |
Rock A. Hudson
|
|
|
garage code 4124 Phone #: ###-#### Inspection requested via web by Darryn Coburn BCC 04-05-24(D)- Inspector shall have access to all boxes. Garage receptacle partially blocked unable to test. 210.8- All garage receptacle outlets shall have GFCI protection. 210.52- A receptacle outlet shall be located with in 6' of wall at top of stair on level 2. 314.17(C)- Where boxes moved for tile NM sheath shall enter box at least 1/4" minimum. 314.25- All boxes shall have a cover. Level 3 mechanical room. 352.30- Service PVC riser shall be secured with in 36" of meter.
|
Rough-In Permanent Service | 3/19/2018 | 3/19/2018 | 3/19/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough in ok p/s u/g n ok
|