Permit Information
Permit NumberELE18-00976
StatusFinaled
Name RUMMER ELECTRIC
Site Address 3761 S CLACTON WAY
Project Name 
Customer Number1573
ePlanReviewNo
Description
Complete Installation (includes room count and per: new house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/30/20187/31/20187/31/2018APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
Rough-In Permanent Service3/16/20183/16/20183/16/2018PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Neal Rumsey corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service3/15/20183/15/20183/15/2018PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
110.3- SER shall be secured by listed strap. Nail strap used listed for conduit only.
210.11(C)(4)- Circuit for garage receptacles shall have no other outlets. transformer.
300.4(B)(1)- Where NM cable passes thru punched or drilled holes a bushing or listed connector shall be installed to protect from physical damage. Furnace.
314.23(B)- Power bath fan hanging on wire. Secure fan in place.
352.46- A listed bushing shall be installed on service PVC riser.
* What is purpose for wire hanging from ceiling by back door?