Final | 6/27/2018 | 6/28/2018 | 6/28/2018 | P | PASS |
Mark Moncarr
|
|
|
Garage code is 7352 Phone #: ###-#### Inspection requested via web by Zane Robertson Ok final.
|
Electrical Rough-In | 5/23/2018 | 5/24/2018 | 5/24/2018 | A | PASS |
Mark Moncarr
|
|
|
Floor heat in master bathroom and hall bath the garage code is 6288 enter Phone #: ###-#### Inspection requested via web by Zane Robertson Ok cover floor heat mstr and main bath. Talked to contractor about pulling cold leads out of wall and installing in floor. I received pics of correct install.
|
Rough-In Permanent Service | 3/20/2018 | 3/20/2018 | 3/20/2018 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson p/s u/g n ok. Corrections made.
|
Rough-In Permanent Service | 3/19/2018 | 3/20/2018 | 3/20/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson 110.3- Power to chime transformer missed. 250.24(A)(5)- Grounded conductor shall not be connected to ground on the loadside of service disconnecting means. Remove grounding electrode conductor from sub panel. 314.17(A)- Open KO in entry 3/0 box. Shall close KO with approved means. 314.25- All boxes shall have covers. Recessed can in powder bath missing junction box cover.
|