Final | 6/27/2018 | 6/28/2018 | 6/28/2018 | A | PASS |
Rock A. Hudson
|
|
|
garage code 2124 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
Rough-In Permanent Service | 3/28/2018 | 3/29/2018 | 3/29/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 3/27/2018 | 3/28/2018 | 3/28/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Installation not complete. Missed recessed con in kitchen area. 314.25- Recessed can junction box covers shall be installed to totally enclose box. Upstairs can back cover not installed as per manufacturers instructions. 300.4- Nail plates needed in kitchen under switch. WUI zone A- Outdoor recessed con fire barriers not complete at time of inspection.
|