Permit NumberELE18-01167
StatusFinaled
Name 45TH PARALLEL ELECTRIC LLC
Site Address 1320 N HARTMAN ST Unit: H-1
Project Name 
Customer Number33033
ePlanReviewNo
Description
Alteration or Repair: electrical rewire after fire, Building H units 1,2,3,4,5,6,8 (unit 7 had no electrical damage or repair and is located on the lower south corner)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/11/20187/12/20187/12/2018APASS
DetailsTom Saunders
Building H, access 6935 Phone #: ###-#### Inspection requested via web by David Nelson...coprrections made...ok to final
Final7/11/20187/11/20187/11/2018PFAIL
DetailsTom Saunders
access 6935 Phone #: ###-#### Inspection requested via web by David Nelson...
unit 1..abrasion protection needs added for romex at bedroom heaters
unit 2..romex protection-heaters
outlets shall not be installed above heater
unit 3..romex protection-heaters
outlets shall not be installed above heater
unit 4 romex protection-heaters
outlets shall not be installed above heater
unit 5..abrasion protection for romex living heater
unit 6..patio light not working
romex protection-heaters
unit 7..living rm heater-junction cover
kitchen outlets need to be completed
panel needs labelled completely
unit 8..panel needs labelled completely
Rough-In Permanent Service3/29/20183/29/20183/29/2018PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by David Nelson...rough ok to cover...p/s, u/g, 2 meter packs, 9 meters, new feeds from transformer needed
Rough-In Permanent Service3/27/20183/28/20183/28/2018AFAIL
DetailsTom Saunders
electrical rewire after fire, building H units 1,2,3,4,5,6,8 Phone #: ###-#### Inspection requested via web by David Nelson...

H8-wires need stapled 1 1/4 back fromface of stud where sheetrock cut out, nail plates at panel
H6- bushing on pipe with feeder wires
H5- nail plates in ceiling
H2- finish wiring for outside light, misc outlets need made up, wires need stapled 1 1/4 back from face of stud 12/2 living rm
H3- exhaust fan wiring needs completed in bath
nail plates needed on sub feed at panel

listed connector at service going from PVC to HUB...both meter packs