Permit NumberELE18-01283
StatusFinaled
Name COBB ELECTRIC
Site Address 2822 E HARD ROCK DR
Project NameBoulder Heights Remodel- BSPS
Customer Number 
ePlanReviewNo
Description
Finish top floor remodel (final Trim for ELE18-00220) finish rough-in and final on bottom floor
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/20/20188/20/20188/20/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Troy Cobb Final ok
Conference8/20/20188/20/20188/20/2018APASS
DetailsJames Ady
Just need to clarify some things from the inspection on Friday. We might be able to handle it with a phone call Phone #: ###-#### Inspection requested via web by Troy Cobb After discussing with Troy, Down bed receps will not need added. Walls were not opened up. All others corrections need addressed.
Final8/16/20188/17/20188/17/2018PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Troy Cobb
BCC 04-05-32- No code violation shall be retained. Hot tub TA, Bonding rain gutter, Missing covers and outdoor covers.
110.3- Reverse polarity washer receptacle.
110.27- All NM located below 8' shall be protected from damage. Master bath, above panel.
210.8- Washer receptacle located with in 6' of a sink shall have GFCI protection.
210.52- Receptacles shall serve wall space 24" and wider and no point measured along floor line shall be more than 6' from a receptacle outlet. Down stairs bed each side of door, master bed each side of fireplace 6' of wall space each side. Room straight back from entry over 12' between receptacle and 1 recept. not workng.
314.20- Spark rings needed for receptacles located in stone where boxes 1/4" or more in non combustible materials.
406.6- All receptacles shall have covers, outdoor back of house and master bed.
410.16- Recessed cons located in master closet area shall have totally enclosed lamps.
680.26(B)(7)- Fixed metal located with in 5" horizontal and 12" vertical of hot tub water edge shall be bonded to hot tub equipment.
Electrical Rough-In4/16/20184/16/20184/16/2018PPASS
DetailsJames Ady
Top floor was already inspected before we took over the job. In case nobody is there the garage door can be raised up by hand. Phone #: ###-#### Inspection requested via web by Troy Cobb entry, soffits and basement ok to cover