Final | 6/5/2018 | 6/6/2018 | 6/6/2018 | A | PASS |
Tom Saunders
|
|
|
If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell...corrections made...ok to final
|
Final | 4/27/2018 | 4/30/2018 | 4/30/2018 | A | FAIL |
Tom Saunders
|
|
|
Please call March at ###-#### for access. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell.. 1..romex shall not be exposed to physical damage..334.15
2..romex shall not be used in wet or damp locations...334.12(B)
3..outlets shall be of weather resistant type..406.9
4..S/O cord shall be rated heavy duty use to wire air compressor or protected from physical damage...needs replaced-is all ready weathered and cracked and cannot be used to wire compressor 5..access to panel is required...unable to verify breaker...panels shall have 3' clearance..readily accessible meaning no tool...110.26
|