Permit Information
Permit NumberELE18-01756
StatusFinaled
Name GLENN ELECTRIC
Site Address 3812 S MILLBROOK WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: ROUGH & PERM SERVICE
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/10/20188/10/20188/10/2018PPASS
DetailsJames Ady
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
Rough-In Permanent Service6/4/20186/4/20186/4/2018PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Bob Glenn Corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service5/31/20186/1/20186/1/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Bob Glenn
210.52- No point measured a along floor line shall exceed 6' from a receptacle outlet. Dining room.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage. Nail plates needed level 3 lower plate under switch and level 1 above entry switches.
314.25- Rcess junction box cover not tight to box on level 2