Permit Information
Permit NumberELE18-02290
StatusFinaled
Name HZ ELECTRIC LLC
Site Address 3332 E ECHO CT
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: WIRING
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/12/20189/12/20189/12/2018PPASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
fInal ok
Rough-In Permanent Service6/19/20186/19/20186/19/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Rough in ok cover p/s u/g n ok
Rough-In Permanent Service6/18/20186/19/20186/19/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
110.3- Unable to confirm listing for non-metallic pancake boxes on exterior. Provde documentation.
210.52- A receptacle outlet shall be located with in 6' of flex room door to patio. nearest one 8'.
300.4 (A)(1)- Cables passing thru holes that do not meaintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Marked with X.
300.4 (B)(1)- Where NM cable enter fireplace it shall be protected by a bushd fitting.
300.4(G)- Where #4 or larger enter an enclosure they shall enter thru a bushed fitting.
Check smoke detector locations, unable to locate print to confirm.
complete make-up, fireplace switches, wirenuts missing switch near office stair.