Permit Information
Permit NumberELE18-02517
StatusFinaled
Name HOFFPAUIR QUENTIN MATHEW
Site Address 5545 S ZONETAILED WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Alteration or Repair: moved/ added wiring in kitchen 7/11/18 TCH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/29/20188/30/20188/30/2018APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Quentin Hoffpaui Corections made final ok
Final8/27/20188/29/20188/29/2018PFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Quentin Hoffpauir 210.8 Kitchen counter receps shall be GFCI protected.(Rt and Lt of cooktop.) 210.52C5Exception. Recep shall not be located more than 6in from counter edge
Final8/27/20188/27/20188/27/2018PNR
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Quentin Hoffpauir
Electrical Rough-In7/10/20187/11/20187/11/2018PPASS
DetailsJames Ady
Garage code 1002. Please call me before heading over.
Thanks,
Quentin Phone #: ###-#### Inspection requested via web by Quentin Hoffpauir Corrections made Kitchen only rough in ok
Electrical Rough-In7/9/20187/10/20187/10/2018PFAIL
DetailsJames Ady
please call 30 minutes before heading out that way.
Thanks Phone #: ###-#### Inspection requested via web by Quentin Hoffpauir 210.11C1 Small appliance circuits shall have no other outlets(Kitchen undercounter lights)