Permit Information
Permit NumberELE18-02777
StatusFinaled
Name APEX ELECTRICAL SERVICES
Site Address 245 S CAPITOL BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: lobby remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/11/201810/11/201810/11/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ryan Wake Final ok
Final9/25/20189/26/20189/26/2018APART
DetailsDaryl DeGrange
Chris ###-#### TCO bar and sitting area. Partial final OK
Final9/25/20189/25/20189/25/2018PPART
DetailsRock A. Hudson
TCO for bar and sitting area ###-#### Chris.
South east side of bar unable to provide GFCI protection for receptacles located on back side for mobile devices and 1 inside bar receptacle due to wiring method used. If unable to GFCI area needed these circuits shall be locked out until compliant with NEC. Bar needs to open evening of 9-25-18. Contractor agrees to complete or lock out. TCO ok
Final9/25/20189/25/20189/25/2018PFAIL
DetailsRock A. Hudson
Partial final bar area please call Chris 9411710 prior to inspection Phone #: ###-#### Inspection requested via web by Ryan Wake
210.8- All 20 amp 120 volt receptacle outlets located within 6' of a sink shall have GFCI protection. GFCI devices shall be installed in a readily accessible location. Receptacles behind appliances and on back side of bar for charging mobile devices.
Electrical Rough-In9/14/20189/14/20189/14/2018PPASS
DetailsRock A. Hudson
Bar rough in inspection Phone #: ###-#### Inspection requested via web by Ryan Wake
Bar wall rough in ok cover
Electrical Rough-In8/16/20188/17/20188/17/2018APASS
DetailsRock A. Hudson
Rough in front entry Phone #: ###-#### Inspection requested via web by Ryan Wake Entrance walls and hardlid and cloud rough in ok cover
Electrical Rough-In8/15/20188/16/20188/16/2018APASS
DetailsRock A. Hudson
Chris is contact. Partial rough in walls and ceiling in lobby. Phone #: ###-#### Inspection requested via web by Ryan Wake
Columns, misc walls and patches, fireplace wall rough in ok cover
Electrical Rough-In8/13/20188/14/20188/13/2018APASS
DetailsDaryl DeGrange
Chris is contact. Ceiling inspection Phone #: ###-#### Inspection requested via web by Ryan Wake Rough-in ok cover hard lid above restaurant area only
Electrical Rough-In8/8/20188/9/20188/9/2018PPASS
DetailsDaryl DeGrange
Rough in dining walls only Inspection requested via web by Ryan Wake rough-in ok cover
Electrical Rough-In8/3/20188/3/20188/3/2018PPASS
DetailsRock A. Hudson
Please call before inspection as I will be in and out. Porte Corche rough in Phone #: ###-#### Inspection requested via web by Ryan Wake
Ceiling noted rough in ok cover