Permit Information
Permit NumberELE18-03212
StatusFinaled
Name SUBLIME ELECTRIC LLC
Site Address 5724 W ELKHORN AVE
Project Name 
Customer NumberDisaster K
ePlanReviewNo
Description
Alteration or Repair: Code upgrade & repair to electrical system
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/25/20191/25/20191/25/2019PPASS
DetailsTom Saunders
Lock box is on the front door, code 1976. If you have any questions please feel free to contact CJ ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan..
corrections made...ok to final
Final1/24/20191/24/20191/24/2019PFAIL
DetailsTom Saunders
There is a lock box on the front door, code 1976. If you have any questions please feel free to contact CJ ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan....
1) luminaire (Fan) on patio shall be rated for damp location - verify 410.10
2) exposed wire at patio fan 422.19
box not rated for fan installation - 422.18
oulet box shall be completely covered - 422.20
Article 410, 410.20, 410.21, 410.10(A)
3) island outlet has no power
4) water heater needs disconnect or breaker lock out - 422.31
5) furnace disconnect shall have permanent marking of ON/OFF - toggle switch
422.34, 422.35
Rough-In Permanent Service10/23/201810/24/201810/24/2018APASS
DetailsEric Story
Lock box code 1976. If you have any questions please feel free to contact Jake ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
Rough-in ok to cover
p/s u/g n ok