Permit Information
Permit NumberELE18-03384
StatusFinaled
Name DG ELECTRIC LLC
Site Address 11324 W EDNA ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: New Construction
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/28/201811/28/201811/28/2018PPASS
DetailsTom Saunders
Garage Code 4053 Phone #: ###-#### Inspection requested via web by Dean Gernaat...
corrections made...ok to final
Final11/26/201811/27/201811/27/2018AFAIL
DetailsRock A. Hudson
Garage Code 4053 Phone #: ###-#### Inspection requested via web by Dean Gernaat 210.8- All 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. 1st nook receptacle to right of kitchen sink.
210.52(C)- Pantry counter work space shall have receptacle outlets located so that no point measured along wall line is more than 24" from a receptacle outlet.
348.30(A)- FMC shall be scured with in 12" of island receptacle box.
404.9(A), 406.6- All garage cover plates shall be installed.
408.4- circuit directory shall be complete. GFCI breaker will not reset.
410.16(A)- LED and incandecent luminaires located in master closet shall have totally enclosed lamps.
Rough-In Permanent Service9/6/20189/7/20189/7/2018APASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Dean Gernaat p/s u/g n ok