Permit Information
Permit NumberELE18-03928
StatusFinaled
Name D C ELECTRICAL SOLUTIONS
Site Address 1420 N 21ST ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/20/20195/21/20195/21/2019APASS
DetailsMark Moncarr
please call 1/2 hour before Phone #: ###-#### Inspection requested via web by Charles Davis Ok final. Corrections made.
Final3/9/20193/11/20193/11/2019AFAIL
DetailsRock A. Hudson
lock box code 2011 Phone #: ###-#### Inspection requested via web by Charles Davis
210.52(C)- For counter top areas in dining room area receptacle outlets shall be installed so that no point measured along wall line is more than 24" from a receptacle outlet. Island not set yet.
314.25- All boxes shall have covers. Furnace box mounted on side needs cover.
410.22- Luminaire boxes shall be covered. Light over sink hanging on wires.
Rough-In Permanent Service10/17/201810/18/201810/18/2018ACANC
DetailsMark Moncarr
Lockbox on back door rail. Code 2011
Smoke dectors are to be wireless. Phone #: ###-#### Inspection requested via web by Charles Davis Added a RI inspection. No p/s. A new panel was installed in basement to replace existing.
Electrical Rough-In10/18/201810/18/201810/18/2018PPASS
DetailsMark Moncarr
Ok cover basement and kitchen. All other locations fished in. Will check on final.