Permit Information
Permit NumberELE18-04276
StatusFinaled
Name MAGIC VALLEY ELECTRIC LLC
Site Address 3139 E BOISE AVE
Project NameHightower Addition
Customer Number15337
ePlanReviewNo
Description
Permanent Service Up to 200 amps ONLY: Relocate existing 200A panel and install a new 200A meter main overhead service and feeders from the meter main to the sub panel.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/16/20198/16/20198/16/2019PPASS
DetailsJames Ady
Call Brodie with any questions. Phone #: ###-#### Inspection requested via web by William Salts Corrections made final ok
Final8/9/20198/12/20198/12/2019PFAIL
DetailsJames Ady
Please call Brodie with any questions Phone #: ###-#### Inspection requested via web by William Salts 210.8 garage receps shall be gfci protected
433 a/c overcurrent shall not exceed max rating on nameplate.
408 Panel schedule shall be acuratly and clearly labeled
422. cord and plug used as disc shal be accessible
110.3. front wheatherproof missing internal trim and also protecting rear w/p
Final8/7/20198/8/20198/8/2019PNR
DetailsJames Ady
Please call Juan with any questions Phone #: ###-#### Inspection requested via web by William Salts Missing item throughout. Not ready re-call
Conference2/13/20192/14/20192/14/2019ACANC
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by William Salts needed rough in
Electrical Rough-In2/14/20192/14/20192/14/2019APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by William Salts Kitchen layout will not change. Exhisting receps locations ok. Corrections made rough in ok
Electrical Rough-In2/12/20192/13/20192/13/2019AFAIL
DetailsRock A. Hudson
Call Wayne with any questions, ###-####.
Phone #: ###-#### Inspection requested via web by William Salts
Corrections not complete, receptacle added in master bed between bath and closet only. Complete rest of corrections and recall
Electrical Rough-In2/8/20192/11/20192/11/2019AFAIL
DetailsJames Ady
Call Wayne with any questions, ###-####. Phone #: ###-#### Inspection requested via web by William Salts 210.52. Recep needed on Garage seperation wall Living room side., Front office, Back side of closet. Master bed between Closet door and Bathroom door. 210.52D within 3ft of 2nd master bath vanity. Remove all wiring from swith in tub footprint.
Electrical Rough-In1/30/20191/30/20191/30/2019PPASS
DetailsJames Ady
Rough in for garage and utility room addition. Please call Wayne at the number listed or Kaden at ###-#### when on the way. Phone #: ###-#### Inspection requested via web by William Salts Garage and utility room only ok to cover
Rough-In Permanent Service11/19/201811/20/201811/20/2018ANR
DetailsJames Ady
Please call Kaden when on the way at ###-####. Phone #: ###-#### Inspection requested via web by William Salts
Permanent Service11/20/201811/20/201811/20/2018PPASS
DetailsJames Ady
Please call Kaden when on the way at ###-####. Phone #: ###-#### Inspection requested via web by William Salts p/s u/g n ok