Final | 2/26/2019 | 2/27/2019 | 2/27/2019 | A | PASS |
James Ady
|
|
|
code 4224 any ? call mike Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
Rough-In Permanent Service | 12/3/2018 | 12/3/2018 | 12/3/2018 | A | PASS |
James Ady
|
|
|
SPECS FOR HOOD VENT WILL BE ON SITE FOR REFERENCE Phone #: ###-#### Inspection requested via web by Bob Glenn Remote blower cable is a listed assembly and installed as per manufacturer instructions. Corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 11/28/2018 | 11/29/2018 | 11/29/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 110.3- All electrical equipment shall be listed for installation. Flexible cord for remote hood motor in 2nd floor attic does not have identification. Open conductors in attic to plug connection in attic. Shall be secured and supported. If listed shall be protected from damage where ran thru bored holes that do not maintain 1 1/4" from framing surface. 314.25- Recessed can in master bath over tub junction box cover shall be completely installed flush with box to totally cover box opening. 334 12 NM cable shall not be installed where subject to physical damage. Under stair installed where drywall will hit when it is installed.
|