Final | 12/11/2018 | 12/12/2018 | 12/12/2018 | A | PASS |
Tom Saunders
|
|
|
key box by front door code 3390 Phone #: ###-#### Inspection requested via web by Darryn Coburn...corrections made...ok to final
|
Final | 12/7/2018 | 12/10/2018 | 12/10/2018 | A | FAIL |
Tom Saunders
|
|
|
AC unit needs inspected. Key box by front door code 3390 Phone #: ###-#### Inspection requested via web by Darryn Coburn... 1..NM cable not approved to be used in wet or damp locations-334.12(B) A/C and service outlet 2..water heater shall have disconnect or breaker lock out installed 3..all outlets serving kitchen counter tops shall be/have GFCI protection-210.8 4..all garage outlets shall be/have GFCI protection-210.8 5..panel shall be legibally and completely labelled as to its clear, evident, and specific purpose or use-408.4
|