Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-00001
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 1003 W MAIN ST
Project NameGood Burger III + The Drop
Customer Number 
ePlanReviewNo
Description
Alteration: Electrical for the Good Burger III & The Drop tenant improvement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/13/20193/13/20193/13/2019PPASS
DetailsRock A. Hudson
CONTACT: MIKE ENNIS Phone #: ###-#### Inspection requested via web by Deb Gooden
Final ok
Final3/12/20193/13/20193/13/2019AFAIL
DetailsRock A. Hudson
Contact: Mike Ennis Phone #: ###-#### Inspection requested via web by Deb Gooden 210.8(B)- 2 Circuits located in kitchen area on south end of bar shall have GFCI protection for personel.
Electrical Rough-In2/7/20192/8/20192/8/2019PPASS
DetailsRock A. Hudson
Contact: Mike Ennis. PM ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Discussed requirement for show window receptacles and circuits. 2 windows with show receptacles noted on print, 2 window not shown on print. All window sections required to have show window receptacles and are wide enough to need dedicated circuits for each receptacle as per 210.62 and 220.14(G).
Hardlid rough in ok cover
Electrical Rough-In1/15/20191/15/20191/15/2019PPASS
DetailsRock A. Hudson
CONTACT: MIKE ENNIS Phone #: ###-#### Inspection requested via web by Deb Gooden
1 north and east windows will be roll up so no show window receptacles required.
Wall rough in ok cover