Permit Information
Permit NumberELE19-00042
StatusFinaled
Name CONLEY ELECTRIC
Site Address 931 S CAPITOLA WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/31/20196/3/20196/3/2019APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Don Conley final ok
Final5/31/20195/31/20195/31/2019PCANC
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Don Conley
Conference5/9/20195/9/20195/9/2019PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Don Conley Talked about recep location over kitchen countertop to the left of cook top. Will put in plug mold on underside of cabinet.
Electrical Rough-In1/7/20191/7/20191/7/2019PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Don Conley....
corrections made...rough ok to cover
Permanent Service1/7/20191/7/20191/7/2019PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Don Conley....inspection done 1/4/19 by James Ady
p/s u/g new ok
Electrical Rough-In1/3/20191/4/20191/4/2019AFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Don Conley 210.52. Recep needed to rt of master bath pocket door and rt of living room slider. 300.4 Nail plates needed inkitchen rt of fridge and right of dining slider. 110.14. Grounding conductors needed tied through in smokes.