Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-00335
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 416 S 9TH ST
Project Name 
Customer Number19202
ePlanReviewNo
Description
New: Fire remodel of performing arts theater area, including power, lighting and fire alarm. Per approved plans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/6/20193/6/20193/6/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jim Noll Final ok
Final3/5/20193/5/20193/5/2019PCANC
DetailsRock A. Hudson
can this please be the last inspection time for the day if possible. thanks Phone #: ###-#### Inspection requested via web by Jim Noll
Jim Noll called and asked to cancel inspection and they would recall. Thanks for heads up.
Final3/5/20193/5/20193/5/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jim Noll
Corrections not all complete. Open boxes up mech., open boxes above stage floor. (Trouble shooting)
Final3/4/20193/4/20193/4/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jim Noll
110.14- Unused openings shall be closed. KO seals electrical room, up stairs mezz, up near bar.
210.62- Show window receptacles required on all windows with 12 linear ft or major fraction there of. 3 entrance windows above doors.
300.15- All splices shall be contained in boxes. Dn hall to bathrooms, up near bar.
314.25- All boxes shall have covers, Entry desk, up mech. up near bar.
Final3/1/20193/1/20193/1/2019PCANC
DetailsRock A. Hudson
please call when you have a time scheduled to come and inspect. thanks Phone #: ###-#### Inspection requested via web by Jim Noll
Jim Noll called and asked to cancel and would reschedule when ready.
Thank you for the heads up.
Conference2/28/20192/28/20192/28/2019PPASS
DetailsRock A. Hudson
Discussed work clearance required for disconnecting means for upstairs mechenical equipment in small room. As per 110.26 minimum width and depth shall be present. As of now 24" width for 2 unfused disconnects.
Conference2/6/20192/6/20192/6/2019PPASS
DetailsRock A. Hudson
Discusssed if conduit run from disconnect to transformer is required to stay out of work space associated with disconnecting means. As per 110.26- work space shall be clear from floor to 6 1/2' minimum height and minimum width and depth of space depending on voltage in front of disconnecting means.
Electrical Rough-In2/6/20192/6/20192/6/2019APASS
DetailsRock A. Hudson
The Knitting Factory wall inspection in concert area. Dimitri Gyteas on site contact. Phone #: ###-#### Inspection requested via web by Jim Noll
North and south pathway lights and receptacles wall rough in ok cover