Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-00652
StatusFinaled
Name SOUTHERN IDAHO ELECTRIC
Site Address 350 N 9TH ST Unit: 100
Project Name 
Customer Number 
ePlanReviewNo
Description
New: electrical for TI per plans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/30/20195/1/20195/1/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
Final4/30/20194/30/20194/30/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
210.8- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Bar. 22/24 2 pole 20 for kitchen not tripping.
300.22- Cooler penatrations shall be sealed.
408.4- Circuit directory shall be complete.
Electrical Rough-In4/24/20194/24/20194/24/2019PPASS
DetailsRock A. Hudson
Grid ceiling Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Bar grid rough in ok cover
Electrical Rough-In4/19/20194/19/20194/19/2019PPART
DetailsRock A. Hudson
grid ceiling Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Kitchen and office grid only rough in ok cover
Electrical Rough-In3/11/20193/12/20193/12/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Hardlids, bar wall, columns rough in ok cover
Electrical Rough-In2/21/20192/22/20192/22/2019PPASS
DetailsMark Moncarr
office, kitchen, bathroom walls Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Ok cover office, baths and kitch area.