Permit Information
Permit NumberELE19-00771
StatusFinaled
Name POWER PLUS INC
Site Address 300 W FORT ST
Project NameFort Boise Renovation
Customer Number1559
ePlanReviewNo
Description
Alteration: Renovation
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/19/20197/22/20197/22/2019APASS
DetailsJames Ady
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Corrections made final ok
Final7/17/20197/18/20197/18/2019AFAIL
DetailsJames Ady
Bill Peace is contact at ###-####, Temp Final?? Phone #: ###-#### Inspection requested via web by Debby Pierce 110.3B and 210.8. Rm 106A nurses Breakroom. Recep on wall Reverse polarity and no GFCI within 6ft of sink. Rm 130- Existing receps on back wall are dead. Kitchen- BBC Section 9-05-32. Violation not to be retained. 110.12A Unused openings shall be closed(Missing KO seal in heater J-Box) 210.8B2. Kitchen receps shall be GFCI protected.(Remove or protect existing receps in kitchen area)
Electrical Rough-In6/13/20196/14/20196/14/2019APASS
DetailsJames Ady
Ceiling Inspection, Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce rooms 130 and 102 Ceiling only ok to cover
Electrical Rough-In6/11/20196/12/20196/12/2019APASS
DetailsJames Ady
Bill Peace is contact at ###-####. Ceiling Inspection. Phone #: ###-#### Inspection requested via web by Debby Pierce Room 132 ceiling only ok to cover
Electrical Rough-In5/3/20195/6/20195/6/2019APASS
DetailsJames Ady
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce room 106A hard lid ok to cover
Electrical Rough-In5/2/20195/3/20195/3/2019APART
DetailsJames Ady
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce 3 Restrooms Ceiling only Ok to cover. 106A Nurses restroom not ready. Burried j box at ceiling.
Electrical Rough-In4/16/20194/17/20194/17/2019APASS
DetailsJames Ady
Andy Chambers is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Classroom devider wall and restroom ok to cover
Electrical Rough-In4/12/20194/12/20194/12/2019PPASS
DetailsJames Ady
Andy Chambers is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Classroom and 2 restrooms, Hard lids only access panels framed ok to cover
Electrical Rough-In4/9/20194/10/20194/10/2019APASS
DetailsJames Ady
Andy Chambers is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Discussed GFCI requirments for kitchen. Half wall in Kitchen only ok to cover