Permit Information
Permit NumberELE19-00774
StatusFinaled
Name STEPHENS ELECTRIC INC
Site Address 4113 W SPAULDING ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Complete wiring for a fully remodeled homne
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/7/20195/8/20195/8/2019APASS
DetailsEric Story
the breaker tie down is installed, it is a new style, its a black plastic piece top center of the panel over the main breaker, please call for any questions, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
Corrections fixed final ok
Final5/1/20195/2/20195/2/2019AFAIL
DetailsEric Story
Ant questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
210.63 Air conditionning equipment shall have a receptacle located within 25' of equipment
408.36(d) Back fed devices shall be secured in place
250.94(a) Intersystem bond device required
Rough-In Permanent Service3/5/20193/6/20193/6/2019APASS
DetailsTom Saunders
Any questions plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren...
rough in ok to cover
p/s o/h new ok