Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-00838
StatusFinaled
Name SPENCER ELECTRIC
Site Address 2894 S CANONERO WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: new const
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/25/20199/26/20199/26/2019APASS
DetailsTom Saunders
corections made and house is ready for final code is 4646enter Phone #: ###-#### Inspection requested via web by ron spen cer...
corrections made...ok to final
Final9/23/20199/24/20199/24/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by ron spen cer
200.6- White conductor used as other than grounded conductor shall be identified other than white in AC disconnect.
210.8(A)- Unable to located GFCI device for christmas receptacle in soffit, exception to outdoor receptacle fed off garage circuit is for readily accessible receptacles only.
210.52(A)- Area above cabinets at each side of fireplace is wall space and shall have a receptacle outlet located with in 6' of fire place. Receptacles located inside cabinets do not count.
210.52(C)- Counter top located in pantry shall have receptacles installed so that at no point measured along wall line is more than 24" from a receptacle outlet.
210.70- Required luminaire located at garage man door not working.
314.23(B)(1)- Island receptacle boxes shall not be secured by screws thru side of boxes.
334.30- NM cable shall be secured with in 12" of island receptacle box.
352.30- PVC service riser shall be secured with in 3' of meter base. strap in place but not secured.
406.6- Outdoor receptacle in use cover on east side of garage not completely secured. Missing screw.
BCC 9-05-17- It shall be unlawful to block electrical inspectors access to electracal associated with dwelling. Move master bed dresser and bed a minimum of 3' from wall to provide access to receptacles.
Rough-In Permanent Service3/12/20193/12/20193/12/2019PCANC
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by ron spen cer...
corrections made
rough ok to cover
p/s u/g new ok
Rough-In Permanent Service3/11/20193/11/20193/11/2019PFAIL
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by ron spen cer...
1..temp outlets installed with screws not approved for box...box shall be replaced..110.3
2..wire shall be free of pinch points and away from truss gang nailers...throughout house..110.12
3..NM cable shall be supported to code...334.30
every 4 1/2 ft. mst bedroom, entry, above panel
4..smoke detectors shall be made up-grounds connected