Permit Information
Permit NumberELE19-00843
StatusFinaled
Name ABBETH LLC
Site Address 1857 E RIDGECREST DR
Project NameAbbeth flip
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Alteration or Repair: Re-route wiring because of moved walls.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/29/20198/30/20198/30/2019PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Daniel Dow Corrections made final ok
Final8/15/20198/16/20198/16/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Daniel Dow
210.8- All receptacles serving kitchen counter top areas shall have GFCI protection. Left of sink. 314.17- Where NM cable enters boxes sheathing shall enter box a minimum of 1/4". Island. Where NM cable enters a metal enclosure abrasion protection shall be provided. AC disconnect.
334.12- NM cable shall not be installed where subject to damage. Island, need conduit protection.
356.30- Non metallic flex shall be secured with in 12" of enclosure. AC whip.
406.5- Receptacles shall be secured to boxes. 1 rt of fireplace and basement family room.
406.9- Outdoor covers shall be extra duty rated.
408.4- Circuit directory shall be complete.
440.6- AC fuse shall not exceed value on name plate. 40 installed 35 max.
Electrical Rough-In3/22/20193/22/20193/22/2019PPASS
DetailsRock A. Hudson
Daniel Phone #: ###-####
Master bed only new bedroom circuit. Smokes on master bedroom circuit.
Rough in ok cover
Conference3/20/20193/20/20193/20/2019PDONE
DetailsJames Ady
Daniel Phone #: ###-#### Covered a lot of topics. Owner has done Electrical work before. Covers needed on all atttic J boxes, receps needed on all patios, Smoke detectors need added.