Permit Information
Permit NumberELE19-00966
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 2015 N CURTIS RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: provide permanent service to portable classroom
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/28/20193/29/20193/29/2019APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Shawna Gates...
ok to final
Permanent Service3/21/20193/21/20193/21/2019PCANC
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Shawna Gates...done AM already...changed final to perm service
Final3/20/20193/21/20193/21/2019ACANC
DetailsTom Saunders
the underground feeder are provided and installed by Idaho power, please remove the feeder issue from our inspection. We have know idea what size they are installing Phone #: ###-#### Inspection requested via web by Shawna Gates...
needed permanent service inspection
please schedule final when power restored
Permanent Service3/21/20193/21/20193/21/2019APASS
DetailsTom Saunders
the underground feeder are provided and installed by Idaho power, please remove the feeder issue from our inspection. We have know idea what size they are installing Phone #: ###-#### Inspection requested via web by Shawna Gates....
p/s u/g new ok
Final3/20/20193/20/20193/20/2019PFAIL
DetailsEric Story
Module building service Phone #: ###-#### Inspection requested via web by Shawna Gates
*Need grounding electrode system installed
*Feeders shall be installed as well to verify sizing
*AFC calc needed(fuses are being used may require on final)
Electrical Rough-In3/20/20193/20/20193/20/2019PPASS
DetailsEric Story
U/G inspection ok to cover, was noted under ELE19-00895 before new permit pulled for power to out building