Information based on query as of Tuesday, August 27, 2024.
Permit Information
Permit NumberELE19-01088
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 415 S 9TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Install new and extend existing receptacles where necessary for new energy upgrades to exterior wall.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/31/20198/1/20198/1/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok
Final7/30/20197/31/20197/31/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kevin Perez
Corrections not complete.
110.22(A)- AC disconnecting means shall be identified as to which AC unit is controlled by which disconnect.
408.4- Panel 2 circuit directory not complete.
Conference7/30/20197/30/20197/30/2019PPASS
DetailsRock A. Hudson
Discussed complete scope of work for office areas. Westerm and most eastern areas have circuitry added for office work stations. As of 12pn 7/30/19 Jimmy with Mountain power has been repairing items listed.
Final7/24/20197/24/20197/24/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kevin Perez
110.3- A double duplex located in conference room not working.
210.63- A service 120 volt 15 or 20 amp receptacle shall be located with in 25' of AC unit. 314.23- Boxes shall be securely mounted. MC and boxes sitting on top of file cabinets.
314.25- 3 open boxes found in eastern open area shall have covers.
408.4- Panel 2 circuit directory shall be complete.
440.11- A disconnecting means shall be provided for newer AC unit.
*BCC 4-05-32- Code violations not to be retained. Checked all unoccupied areas.
Electrical Rough-In3/28/20193/29/20193/29/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kevin Perez
Perimeter walls rough in ok cover