Final | 4/25/2019 | 4/26/2019 | 4/26/2019 | A | PASS |
Rock A. Hudson
|
|
|
Door lock box code: 5584 Phone #: ###-#### Inspection requested via web by Nick Avery Final ok
|
Final | 4/19/2019 | 4/22/2019 | 4/22/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Code for door lock box 5584. Phone #: ###-#### Inspection requested via web by Nick Avery 210.11- Bathroom receptacle outlets shall be fed by a dedicated 20 amp circuit as noted to previous contractor on 6-15-18. 210.52- A receptacle outlet shall be located with in 24" of left side of kitchen sink. 314.20- Where boxes are mounted in non combustible wall cover and are recessed more than 1/4" a spark ring shall be installed. 408.4- Circuit directory shall accurately describe circuitd function. *Dining light hanging on wires, several lights not working.
|