Permit Information
Permit NumberELE19-01227
StatusFinaled
Name R M E INC
Site Address 645 E GOWEN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Power and lighting for new TI per plans.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/1/20197/2/20197/2/2019APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Tyler Bowen
Items as noted corrected...
Occ card signed
Final6/28/20197/1/20197/1/2019APART
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Tyler Bowen 440.22C Max overcurrent shall not exceed manufacturer values.( 2 RTU's fused at 20A need 15A, Mini split fused at 30A needs 20A) Partial final only ok
Electrical Rough-In6/19/20196/20/20196/20/2019APASS
DetailsJames Ady
ceiling cover for remaining two high ceilings. Phone #: ###-#### Inspection requested via web by Tyler Bowen 14ft ceiling only ok to cover
Electrical Rough-In6/13/20196/14/20196/14/2019APASS
DetailsJames Ady
Ceiling Cover - Low Ceiling Phone #: ###-#### Inspection requested via web by Tyler Bowen Ceiling only Marked on lighting print. Side A or South sided
Permanent Service6/3/20196/4/20196/4/2019ACANC
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Tyler Bowen
Electrical Rough-In6/4/20196/4/20196/4/2019PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Tyler Bowen Checked Grounding/Bonding of tranfsormers. Ok to energize
Electrical Rough-In5/1/20195/3/20195/3/2019APASS
DetailsJames Ady
Wall Cover Phone #: ###-#### Inspection requested via web by Tyler Bowen Remaining interior office walls only ok to cover
Electrical Rough-In4/24/20194/26/20194/26/2019APASS
DetailsEric Story
Wall Cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Exterior walls and conference room and extrerior offices minus interoir ok to cover
Electrical Rough-In4/8/20194/8/20194/8/2019PPASS
DetailsJames Ady
underground floor box and east walls. Phone #: ###-#### Inspection requested via web by Tyler Bowen East wall and underground in conference rooms ok to cover